PART 5 — ENVIRONMENTAL SEPARATIONUpdated for the 2024 Ontario Building Code

5.9.2.4.Heat Transfer

(1) Windows, doors and skylights shall meet the heat transfer performance requirements stated in Section 5.3. (See Note A-5.3.1.2.)) (2) Except as provided in Sentence (3), all metal-framed glazed assemblies separating interior conditioned space from interior unconditioned space or exterior space shall incorporate a thermal break to minimize condensation. (3) Metal-framed glazed assemblies need not comply with Sentence (2) where these assemblies are (a) storm windows or doors, or (b) windows or doors that are required to have a fire-protection rating. (See Note A-5.9.2.4.(3))

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.