5.8.1.1.Required Protection

(1) Except as provided in Sentence (2), a dwelling unit shall be separated from every other space in a building in which noise may be generated by (a) a separating assembly and adjoining constructions, which, together, provide an apparent sound transmission class (ASTC) rating not less than 47, or (b) a separating assembly that provides a sound transmission class (STC) rating of not less than 50 and adjoining constructions that conform to Article 9.11.1.4. (2) Construction separating a dwelling unit from an elevator shaft or a refuse chute shall have an STC rating not less than 55.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.