PART 4 — STRUCTURAL DESIGNUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
4.1.7.12.Attached Canopies on Low Buildings with a Height H ≤ 20 m
(See Note A-4.1.7.12.)
(1) For the purposes of this Article, “attached canopy” shall mean a horizontal canopy with a maximum slope of 2% that
is attached to a building wall at any height, hc, above ground level.
(2) The specified external wind pressure, p, and the specified net external wind pressure, pnet, for attached canopies on
exterior walls of low buildings with a height H ≤ 20 m shall be determined as follows:
p = IW qCe Ct Cg Cp , and
pnet = Iw qCe Ct (Cg Cp )
net
where
p = specified external wind pressure acting statically and in a direction normal to the upper or lower surface
of the canopy, considered positive when acting towards the surface and negative when acting away from
the surface,
pnet = specified net external wind pressure acting statically on the canopy, considered positive when acting in a
downward direction and negative when acting in an upward direction,
IW, q, Ce, Ct = as defined in Sentence 4.1.7.3.(1),
CgCp = gust pressure coefficient on the upper or lower surface of the canopy, as given in Figure 4.1.7.12.-A, and
(CgCp)net = net gust pressure coefficient on the canopy, considering simultaneous contributions from the upper and
lower surfaces of the canopy, as given in Figure 4.1.7.12.-B.
Figure 4.1.7.12.-A
Gust Pressure Coefficients on the Upper and Lower Surfaces of Attached Canopies
With no Gap Between the Canopy and the Building
Forming Part of Sentence 4.1.7.12.(2)
Notes to Figure 4.1.7.12.-A:
(1) The coefficients apply for any roof slope, a.
(2) The reference height, h, is the mid-height of the roof or 6 m, whichever is greater.
(3) Positive CgCp values denote forces acting towards the upper or lower surface of the canopy, whereas negative CgCp values denote forces acting away
from the surface. Each structural element must be designed to resist both the positive and negative forces.
Figure 4.1.7.12.-B
Net Gust Pressure Coefficients on Attached Canopies, Considering Simultaneous Contributions from the Upper and
Lower Surfaces of the Canopy
Forming Part of Sentence 4.1.7.12.(2)
Notes to Figure 4.1.7.12.-B:
(1) The coefficients apply for any roof slope, .
(2) The reference height, h, is the mid-height of the roof or 6 m, whichever is greater.
(3) Positive (CgCp)net values denote net forces acting in a downward direction on the canopy, whereas negative (CgCp)net values denote net forces acting in an
upward direction on the canopy. The canopy must be designed to resist both the positive and negative net forces.
← Previous4.1.7.11. Exterior Ornamentations, Equipment and AppendageNext →4.1.7.13. Roof-Mounted Solar Panels on Buildings of Any He
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.