4.1.6.10.Arch Roofs, Curved Roofs and Domes
(1) For all arch roofs, curved roofs and domes, the full and partial load cases defined in Article 4.1.6.3. shall be
considered.
(2) For arch roofs, curved roofs and domes with rise-to-span ratio h/b > 0.05 (See Figure 4.1.6.10.-A), the load cases
provided in Sentences (3) to (7) shall also be considered.
(3) For arch roofs with a slope at the edge αe ≤ 30° (See Figure 4.1.6.10.-A and Table 4.1.6.10.), Ca shall be
(a) taken as 0 on the upwind side of the peak, and
(b) on the downwind side of the peak, taken as
xh h
Ca = 2
for 0.05 < ≤ 0.12 and
0.03Cb b b
4x h
Ca = for > 0.12
Cb b b
where
x = horizontal distance from the roof peak,
h = height of arch, and
b = width of arch.
Figure 4.1.6.10.-A
Accumulation Factors for Arch Roofs and Curved Roofs
Forming Part of Sentences 4.1.6.10.(2) to (4)
Notes to Figure 4.1.6.10.-A:
(1) Refer to Table 4.1.6.10. for applicable values of Cw and Sentences 4.1.6.2.(5) and (6) for applicable values of Cs.
Table 4.1.6.10.
Load Cases for Arch Roofs, Curved Roofs and Domes
Forming Part of Sentences 4.1.6.10.(3), (4) and (9)
Factors
Arch Roofs,
Range of Curved Roofs Arch and Curved Roofs Domes
Load Case
Application and Domes
Ca Ca Ca
Cw
Upwind Side Downwind Side Downwind Side
As stated in
Case I All values of h/b 4.1.6.2.(3) 1.0 1.0 1.0
and (4)
xh h
Slope at edge ≤ 30° Ca = 2
for ≤ 0.12
0.03Cb b b
h/b > 0.05 1.0 0.0
all values of x 4x h
Ca = for > 0.12
Cb b b
xh h
Slope at edge > 30° Ca = for ≤ 0.12
0.06Cb x30 b b y
Case II h/b > 0.05 1.0 0.0 Ca (x, y) = Ca (x, 0) (1 − )
0 < x < x30 2x h r
Ca = for > 0.12
Cb x30 b
h h
Slope at edge > 30° Ca = for ≤ 0.12
0.06Cb b b
h/b > 0.05 1.0 0.0
x ≥ x30 2 h
Ca = for > 0.12
Cb b
(4) For arch roofs with a slope at the edge αe > 30° (See Figure 4.1.6.10.-A and Table 4.1.6.10.), Ca shall be
(a) taken as 0 on the upwind side of the peak, and
(b) on the downwind side of the peak,
(i) for the part of the roof between the peak and point where the slope α = 30°, taken as,
xh h
Ca = for 0.05 < ≤ 0.12, and
0.06Cb x30 b b
2x h
Ca = for > 0.12
Cb x30 b
where
x, h, b = as specified in Sentence (2), and
x30 = value of x where the slope α = 30°, and
(ii) for the part of the roof where the slope α > 30°, taken as,
h h
Ca = for 0.05 < ≤ 0.12, and
0.06Cb b b
2 h
Ca = for > 0.12
Cb b
(5) Except as provided in Sentence (6), Ca for curved roofs shall be determined in accordance with the requirements for
arch roofs stated in Sentences (3) and (4).
(6) Where the slope, α, of a curved roof at its peak is greater than 10°, Ca shall be determined in accordance with the
requirements for gable roofs stated in Article 4.1.6.9. using a slope equal to the mean slope of the curved roof.
(7) For domes of circular plan form (see Figure 4.1.6.10.-B), Ca shall
(a) along the central axis parallel to the wind, vary in the same way as for an arch roof with the same rise-to-span ratio,
h/b, and
(b) off this axis, vary according to
y
Ca (x, y) = Ca (x, 0) (1 − )
r
where
Ca(x,y) = value of Ca at location (x,y),
Ca(x,0) = value of Ca on the central axis parallel to the wind,
x = distance along the central axis parallel to the wind,
y = horizontal coordinate normal to the x direction, and
r = radius of dome.
Figure 4.1.6.10.-B
Unbalanced Snow Accumulation Factor on a Circular Dome
Forming Part of Sentence 4.1.6.10.(7)
Notes to Figure 4.1.6.10.-B:
(1) Refer to Table 4.1.6.10. for applicable values of Cw and Sentences 4.1.6.2.(5) and (6) for applicable values of Cs.
(2) Refer to Sentences 4.1.6.10.(3) and (4) for the calculation of Ca(x,0).
(8) For all arch roofs, curved roofs and domes, the slope factor, C s, shall be as prescribed in Sentences 4.1.6.2.(5)
and (6).
(9) For all arch roofs, curved roofs and domes, the wind exposure factor, C w, shall be as prescribed in Table 4.1.6.10.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.