4.1.3.4.Serviceability
(1) A building and its structural components shall be checked for serviceability limit states as defined in
Clause 4.1.3.1.(1)(a) under the effect of service loads for serviceability criteria specified or recommended in
Articles 4.1.3.5. and 4.1.3.6. and in the standards listed in Section 4.3. (See Note A-4.1.3.4.(1))
(2) The effect of service loads on the serviceability limit states shall be determined in accordance with this Article and
the load combinations listed in Table 4.1.3.4., the applicable combination being that which results in the most critical
effect.
(3) Other load combinations that must also be considered are the principal loads acting with the companion loads taken
as zero.
(4) Deflections calculated for load types P, T and H, if present, with load factors of 1.0 shall be included with the
calculated deflections due to principal loads.
(5) The determination of the deflection shall consider the following:
(a) for materials that result in increased deformations over time under sustained loads, the deflection calculation shall
consider the portion of live load, L, that is sustained over time, Ls, and the portion that is transitory, Lt, and
(b) the calculated deflection due to dead load, D, and sustained live load, Ls, shall be increased by a creep factor as
specified in the standards listed in Section 4.3. to obtain the additional long-term deflection.
(6) The determination of the long-term settlement of foundations shall consider the following:
(a) for foundation soil types that result in increased settlement over time under sustained loads, the additional long-term
settlements shall be determined for the portion of live load, L, that is sustained over time, Ls, and the portion that is
transitory, Lt, and
(b) the additional long-term settlements due to dead load, D, and sustained live loads, Ls, shall be calculated from the
foundation soil properties provided by a qualified professional geotechnical engineer.
Table 4.1.3.4.
Loads and Load Combinations for Serviceability
Forming Part of Sentence 4.1.3.4.(2)
Load Combinations
Limit State Structural Parameter Load Case
Principal Loads Companion Loads
Deflection of the structure 1 1.0D + 1.0L 0.3W or 0.35S
Deflection for materials
or of components of the 2 1.0D + 1.0W 0.35L(2) or 0.35S
not subject to creep
structure(1) 3 1.0D + 1.0S 0.3W or 0.35L(2)
Total deflection of the 1 1.0D + 1.0Ls(4) + 1.0Lt(5) 0.3W or 0.35S
Deflection for materials structure or of
2 1.0D + 1.0W 0.35L(2) or 0.35S
subject to creep components of the
structure(3) 3 1.0D + 1.0S 0.3W or 0.35L(2)
Vibration serviceability Acceleration (6)
Notes to Table 4.1.3.4.:
(1) The calculated deflection due to dead load, D, is permitted to be excluded where specified in the standards listed in Section 4.3.
(2) The companion load factor of 0.35 for live load, L, shall be increased to 0.5 for storage areas, equipment areas and service rooms.
(3) The calculated immediate deflection due to dead load, D, is permitted to be excluded where specified in the standards listed in Section 4.3.
(4) Ls = sustained portion of the live load, L.
(5) Lt = transitory portion of the live load, L.
(6) See Note A-Table 4.1.3.4.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.