3.2.8.1.Application
(1) Except as permitted by Article 3.2.8.2. and Sentence 3.3.4.2.(3), the portions of a floor area or a mezzanine that do
not terminate at an exterior wall, a firewall or a vertical shaft shall
(a) terminate at a vertical fire separation having a fire-resistance rating not less than that required for the floor
assembly and extending from the floor assembly to the underside of the floor or roof assembly above, or
(b) be protected in conformance with the requirements of Articles 3.2.8.3. to 3.2.8.8.
(2) The penetration of a floor assembly by an exit or a vertical service space shall conform to the requirements of
Sections 3.4., 3.5. and 3.6.
(3) A floor area containing sleeping rooms in a building of Group B, Division 2 major occupancy shall not be
constructed as part of an interconnected floor space.
← Previous3.2.7.10. Protection of Electrical ConductorsNext →3.2.8.2. Exceptions to Special Protection
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.