PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.7.9.Emergency Power for Building Services
(1) An emergency power supply capable of operating under a full load for not less than 2 h shall be provided by an
emergency generator for
(a) every elevator serving storeys above the first storey in a building that is more than 36 m high measured between
grade and the floor level of the top storey and every elevator for firefighters in conformance with Sentence (2),
(b) except as provided in Sentence (4), equipment that supplies water for fire suppression as required by Articles
← Previous3.2.7.8. Emergency Power for Fire Alarm SystemsNext →3.2.5.7. and 3.2.5.8. and Sentences 3.2.5.12.(1) and (2)
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.