3.2.7.7.Fuel Supply Shut-Off Valves and Exhaust Pipes
(1) If a liquid or gas fuel-fired engine or turbine for an emergency electric power supply is dependent on a fuel supply
from outside the building, the fuel supply shall be provided with a suitably-identified separate shut-off valve outside the
building.
(2) Where pipes for exhaust gases from emergency power systems penetrate required fire separations, they shall be
enclosed in a separate service space having a fire-resistance rating equal to that of the penetrated floor assembly, but not
less than 45 min.
← Previous3.2.7.6. Emergency Power for HospitalsNext →3.2.7.8. Emergency Power for Fire Alarm Systems
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.