PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.6.6.Venting to Aid Firefighting
(1) Means of venting each floor area to the outdoors shall be provided by windows, wall panels, smoke shafts or, except
as provided by Sentence (5), the building exhaust system.
(2) Fixed glass windows shall not be used for the venting required by Sentence (1) if the breaking of the windows could
endanger pedestrians below.
(3) Openable windows used for the venting required by Sentence (1) shall be permanently marked so that they are easily
identifiable.
(4) Elevator hoistways shall not be designed for the venting required by Sentence (1).
(5) In a building that is not sprinklered, venting of floor areas required in Sentence (1) shall not be provided by the
building exhaust system.
← Previous3.2.6.5. Elevator for Use by FirefightersNext →3.2.6.7. Central Alarm and Control Facility
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.