3.2.6.4.Emergency Operation of Elevators
(1) Manual emergency recall shall be provided for all elevators serving storeys above the first storey.
(2) Key-operated switches for emergency recall described by Sentence (1) shall be provided in a conspicuous location at
(a) each elevator lobby on the recall level, and
(b) the central alarm and control facility required by Article 3.2.6.7.
(3) In-car emergency service switches shall be provided in all elevator cars.
(4) Keys to operate the switches required by Sentences (2) and (3) shall be
(a) provided in a suitably identified box conspicuously located on the outside of an elevator hoistway near the central
alarm and control facility required by Article 3.2.6.7., and
(b) kept at the central alarm and control facility.
(5) In a building that is not sprinklered, automatic emergency recall operation shall be provided for all elevators serving
storeys above the first storey.
(6) The automatic emergency recall feature in Sentence (5) shall be actuated by
(a) smoke detectors installed in each elevator lobby on each storey, or (See Note A-3.2.6.4.(6)(a))
(b) the building fire alarm system.
(7) Smoke detectors in Sentence (6) shall be designed as part of the building fire alarm system.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.