3.2.5.3.Roof Access
(1) On a building more than 3 storeys in building height where the slope of the roof is less than 1 in 4, all main roof
areas shall be provided with direct access from the floor areas immediately below, either by
(a) a stairway, or
(b) a hatch not less than 550 mm by 900 mm with a fixed ladder.
(2) Clearance and access around roof signs or other obstructions shall provide
(a) a passage not less than 900 mm wide by 1 800 mm high, clear of all obstructions except for necessary horizontal
supports not more than 600 mm above the roof surface,
(i) around every roof sign, and
(ii) through every roof sign at locations not more than 15 m apart, and
(b) a clearance of not less than 1 200 mm between any portion of a roof sign and any opening in the exterior wall face
or roof of the building in which it is erected.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.