PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code

3.2.5.10.Hose Connections

(1) Hose connections shall be located in exits, in accordance with NFPA 14, “Standard for the Installation of Standpipe and Hose Systems.” (2) Hose connections are not required within a floor area. (3) Hose connections shall be provided with sufficient clearance to permit the use of a standard fire department hose key. (4) Except as permitted by Sentence (5), 64 mm diam hose connections shall be installed in a standpipe system. (5) Hose connections for 64 mm diam hose are not required in a building that is not more than 25 m high, measured between grade and the ceiling level of the top storey and in which an automatic sprinkler system is not installed.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.