3.2.4.6.Silencing of Alarm Signals
(1) Except as permitted by Sentence (3), a fire alarm system shall be designed so that when an alarm signal is actuated,
it cannot be silenced automatically before a period of time has elapsed that is not less than
(a) 5 min for a building not required to be equipped with an annunciator, and
(b) 20 min for any other building.
(2) Except as permitted by Sentences 3.2.4.18.(8) and Sentences 3.2.4.22.(2) and (3), a fire alarm system shall not
incorporate manual silencing switches other than those installed inside the fire alarm control unit. (See Note A-
3.2.4.6.(2))
(3) Except as provided by Clause 3.2.4.22.(3)(a), in a care and treatment occupancy an alert signal is permitted to be
silenced automatically after 1 min.
← Previous3.2.4.5. Installation and Verification of Fire Alarm SystNext →3.2.4.7. Signals to Fire Department
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.