PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.3.5.Wall With Limiting Distance Less Than 1.2 m
(1) Openings in a wall that has a limiting distance less than 1.2 m shall be protected by closures whose fire-protection
rating is in conformance with the fire-resistance rating required for the wall.
(2) Wired glass or glass block shall not be used for a closure referred to in Sentence (1).
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.