3.2.3.2.Area of Exposing Building Face
(1) Except as permitted by Sentences (2) and (3), the area of an exposing building face shall be calculated as the total
area of exterior wall facing in one direction on any side of a building measured from the finished ground level to the
uppermost ceiling.
(2) If a building is divided by fire separations into fire compartments, the area of exposing building face is permitted to
be calculated for each fire compartment provided the fire separations have a fire-resistance rating not less than 45 min.
(3) In a building that is sprinklered throughout and contains an interconnected floor space, the area of the exposing
building face for the interconnected floor space is permitted to be determined by considering each storey as a separate fire
compartment notwithstanding openings through the floor assemblies.
← Previous3.2.3.1. Limiting Distance and Area of Unprotected OpeninNext →3.2.3.3. Wall Enclosing Attic or Roof Space
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.