PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.3.13.Protection of Exit Facilities
(1) Except as required by Sentence (3) and as permitted by Sentence 3.4.4.3.(1), if the plane of an exterior wall of an
exit enclosure forms an angle less than 135 with the plane of an exterior wall of the building it serves, and an opening in
the exterior wall of the exit enclosure could be exposed to fire from an opening in the exterior wall of the building, the
opening in either the exterior wall of the exit or the exterior wall of the building shall be protected in conformance with
the requirements of Sentence (4) where the opening in the exterior wall of the building is within 3 m horizontally and
(a) less than 10 m below an opening in the exterior wall of the exit, or
(b) less than 2 m above an opening in the exterior wall of the exit.
(See Note A-3.2.3.14.(1))
(2) If an unenclosed exterior exit stair or ramp could be exposed to fire from an opening in the exterior wall of the
building it serves, the opening in the exterior wall of the building shall be protected in conformance with the requirements
of Sentence (4) where the opening in the exterior wall of the building is within 3 m horizontally and
(a) less than 10 m below the exit stair or ramp, or
(b) less than 5 m above the exit stair or ramp.
(3) Except as permitted by Sentence 3.4.4.3.(1), if an exterior exit door in one fire compartment is within 3 m
horizontally of an opening in another fire compartment and the exterior walls of these fire compartments intersect at an
exterior angle of less than 135, the opening shall be protected in conformance with the requirements of Sentence (4).
(4) The opening protection referred to in Sentences (1) to (3) shall consist of
(a) glass block conforming to the requirements of Article 3.1.8.16.,
(b) a wired glass assembly conforming to MMAH Supplementary Standard SB-2, “Fire Performance Ratings,” or
(c) a closure conforming to the requirements of Subsection 3.1.8. and Articles 3.2.3.1. and 3.2.3.14.
← Previous3.2.3.12. Area Increase for Unprotected OpeningsNext →3.2.3.14. Wall Exposed to Another Wall (See Note A-3.2.3.1
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.