3.2.2.76.Group F, Division 2, Any Height, Any Area, Sprinklered
r1 (1) Except as permitted by Articles 3.2.2.77. to 3.2.2.81. and 3.2.2.93., a building classified as Group F, Division 2 shall
conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible
construction, and
(a) except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building shall be sprinklered throughout,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the
supported assembly.
← Previous3.2.2.75. Group F, Division 1, One StoreyNext →3.2.2.77. Group F, Division 2, up to 4 Storeys, Increased
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.