PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.2.60.Group D, up to 6 Storeys, Sprinklered
(1) A building classified as Group D is permitted to conform to Sentence (2) provided
(a) it is sprinklered throughout,
(b) it is not more than 6 storeys in building height,
(c) it has a height of not more than 18 m measured between the floor of the first storey and the uppermost floor level
that does not serve a rooftop enclosure for elevator machinery, a stairway or a service room used only for service to
the building, and
(d) it has a building area of not more than
(i) 18 000 m2 if 1 storey in building height,
(ii) 9 000 m2 if 2 storeys in building height,
(iii) 6 000 m2 if 3 storeys in building height,
(iv) 4 500 m2 if 4 storeys in building height,
(v) 3 600 m2 if 5 storeys in building height, or
(vi) 3 000 m2 if 6 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible
construction used singly or in combination, and
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) roof assemblies shall have a fire-resistance rating not less than 1 h,
(c) except as provided by Sentence (3), where the roof assembly has a height greater than 25 m measured from the floor
of the first storey to the highest point of the roof assembly, the roof assembly shall be constructed of noncombustible
construction or fire-retardant-treated wood conforming to Article 3.1.4.5.,
(d) mezzanines shall have a fire-resistance rating not less than 1 h, and
(e) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the
supported assembly.
(3) Where buildings conforming to Sentence (2) include non-contiguous roof assemblies at different elevations, the roof
assemblies are permitted to be evaluated separately to determine which ones are required to be constructed in accordance
with Clause (2)(c).
(4) Group A, Division 2 major occupancies, Group E major occupancies, Group F, Division 2 and 3 major occupancies
and storage garages located in a building or part thereof within the scope of this Article are permitted to be constructed in
accordance with this Article, provided
(a) the Group A, Division 2 major occupancy, Group E major occupancy and Group F, Division 2 or 3 major
occupancy are located below the third storey, and
(b) storage garages are located below the fourth storey. (See also Article 4.4.2.1.)
(See Note A-3.2.2.51.(5) and 3.2.2.60.(4))
← Previous3.2.2.59. Group D, up to 6 Storeys, Sprinklered, NoncombusNext →3.2.2.61. Group D, up to 4 Storeys, Sprinklered
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.