3.2.2.6.Multiple Major Occupancies

r1 (1) Except as permitted by Articles 3.2.2.7. and 3.2.2.8., and Sentences 3.2.2.48.(4), 3.2.2.51.(5), 3.2.2.57.(3) and 3.2.2.60.(4) and 3.2.2.93.(5) to (7), in a building containing more than one major occupancy, the requirements of this Subsection for the most restricted major occupancy contained shall apply to the whole building. (2) For the purposes of Sentence (1), a retirement home is deemed to be a separate major occupancy. r1 (3) In a building or part thereof constructed in conformance with Article 3.2.2.48., 3.2.2.57. or 3.2.2.93. containing more than one major occupancy, the most restrictive encapsulation requirements of Article 3.1.6.4. and Table 3.2.2.93. for any major occupancy contained within a storey shall apply to the encapsulation required on the interior of a public corridor or exit within that storey.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.