3.2.2.50.Group C, up to 4 Storeys, Noncombustible Construction
(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided
(a) it is not more than
(i) 3 storeys in building height, or
(ii) 4 storeys in building height provided there is not more than one dwelling unit above another dwelling unit,
and vertical fire separations of adjacent dwelling units conform to Sentence (4), and
(b) it has a building area not more than the value in Table 3.2.2.50.
Table 3.2.2.50.
Maximum Building Area, Group C, up to 4 Storeys
Forming Part of Sentence 3.2.2.50.(1)
Maximum Area, m2
No. of Storeys
Facing 1 Street Facing 2 Streets Facing 3 Streets
1 not limited not limited not limited
2 6 000 not limited not limited
3 4 000 5 000 6 000
4 3 000 3 750 4 500
(2) The building referred to in Sentence (1) shall be of noncombustible construction, and
(a) except as permitted by Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less
than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the
supported assembly.
(3) In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence
3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling
units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) The dwelling units described in Subclause (1)(a)(ii) shall be separated by continuous vertical fire separations that
extend through all storeys and service spaces of the separated portions.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous3.2.2.49. Group C, up to 6 Storeys, Sprinklered, NoncombusNext →3.2.2.51. Group C, up to 6 Storeys, Sprinklered, Combustib
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.