3.2.2.45.Group B, Division 3, Up to 2 Storeys, Sprinklered
(1) A building classified as Group B, Division 3 is permitted to conform to Sentence (2) provided
(a) except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building is sprinklered throughout,
(b) it is not more than 2 storeys in building height, and
(c) it has a building area not more than
(i) 2 400 m2 if 1 storey in building height, or
(ii) 1 600 m2 if 2 storeys in building height.
(2) The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible
construction used singly or in combination, and
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,
(b) mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and
(c) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the
supported assembly.
← Previous3.2.2.44. Group B, Division 3, Up to 3 Storeys, SprinklereNext →3.2.2.46. Group B, Division 3, One Storey, Sprinklered
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.