PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.2.34.Group A, Division 3, One Storey
(1) A building classified as Group A, Division 3 is permitted to be of combustible construction or noncombustible
construction used singly or in combination, provided
(a) it is not more than 1 storey in building height, and
(b) it has a building area not more than
(i) 1 000 m2 if facing one street,
(ii) 1 250 m2 if facing 2 streets, or
(iii) 1 500 m2 if facing 3 streets.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.