PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.2.2.24.Group A, Division 2, up to 6 Storeys, Any Area, Sprinklered
(1) A building classified as Group A, Division 2, that is not limited by building area, is permitted to conform to
Sentence (2) provided
(a) except as permitted by Sentences 3.2.2.7.(1) and 3.2.2.18.(2), the building is sprinklered throughout, and
(b) it is not more than 6 storeys in building height.
Division B – Part 3 58a
58b Division B – Part 3
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible
construction, and
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) all loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the
supported assembly.
← Previous3.2.2.23. Group A, Division 2, Any Height, Any Area, SprinNext →3.2.2.25. Group A, Division 2, up to 2 Storeys
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.