PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.17.1.1.Application
(1) This Section applies to the design, erection, assembly and installation of a demountable stage where
(a) the aggregate area of all platforms of the demountable stage is more than 60 m2 and any part of its platforms is more
than 3 m in height above adjacent ground level,
(b) the aggregate area of all platforms of the demountable stage is more than 225 m2, or
(c) any part of the platforms or any roof, wall or structure attached to or located on any of the platforms of the
demountable stage is 5 m or more in height above adjacent ground level.
(2) This Section applies to the design, erection, assembly and installation of a demountable support structure where the
demountable support structure
(a) is more than 3 m in height above adjacent ground level,
(b) is designed to carry a superimposed specified load greater than 115 kg, or
(c) would create a hazard to the public.
(3) Except as provided in this Section, demountable stages and demountable support structures are exempt from
complying with the requirements of this Division.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.