PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.16.2.2.Construction
(1) Where the height of a shelf and rack storage system, measured from the floor supporting the system to the topmost
portion of the shelf, exceeds 18 m,
(a) a fire alarm and detection system conforming to Subsection 3.2.4. shall be installed with
(i) manual stations located at all exit doors including exit doors serving elevated decks and walkways, and
(ii) smoke detectors located, at the ceiling of all rooms and areas containing the shelf and rack storage system,
within exit stair enclosures at the top, and at every third level of elevated deck or walkway, and
(b) the fire alarm and detection system required by Clause (a), shall be designed to notify the fire department upon
activation, and
(c) the shelf and rack storage system shall be designed only for the storage of Class I, II and III commodities as defined
in NFPA 13, “Standard for the Installation of Sprinkler Systems.”
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.