3.14.2.3.Spatial Separation
(1) Except as provided in Sentences (2) to (5), air-supported structures shall not be erected closer than 3 m to other
structures on the same property or to the property line.
(2) Air-supported structures not occupied by the public need not be separated from one another, and are permitted to be
erected closer than 3 m from other structures on the same property where such closer spacing does not create a hazard to
the building occupants or the public.
(3) Except as provided in Sentence (4), an air-supported structure is permitted to be attached to another building
provided the building to which it is attached
(a) conforms to the requirements of other Parts of this Division based on the total building areas of the air-supported
structure and the attached building,
(b) is sprinklered throughout, and
(c) is separated from the air-supported structure by a fire separation having a fire-resistance rating of not less than 1 h.
(4) An air-supported structure is permitted to be attached to another building provided the building to which it is
attached
(a) has a building area not more than 200 m2,
(b) conforms to the requirements of other Parts of the Code based on the building area of the attached building, and
(c) is sprinklered or separated from the air-supported structure by a fire separation having a fire-resistance rating of
not less than 1 h.
(5) Where an air-supported structure is to be constructed in proximity to existing above ground electrical conductors,
the air-supported structure shall be constructed in accordance with Article 3.1.20.1.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.