PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.12.5.1.Lighting and Emergency Provisions
(1) In addition to the requirements of this Subsection, public spas shall comply with the requirements of Sentences
3.11.10.1.(1) to (6).
(2) An emergency telephone directly connected to an emergency service or to the local telephone utility shall be
installed within 30 m of the public spa.
(3) All pumps used in a public spa shall be capable of being deactivated by an emergency stop button that is
(a) clearly labelled, and
(b) located at a point that is
(i) readily accessible to and within sight of persons using the public spa, and
(ii) within 15 m of the public spa.
(4) The emergency stop button required in Sentence (3) shall
(a) be a switch separate from the public spa’s timing device,
(b) activate an audible and a visual signal when used, and
(c) have an emergency sign conforming to Sentence 3.11.10.1.(14).
(5) If a public spa and public pool are located in the same room or space, the emergency stop buttons required in
Sentences (3) and 3.11.10.1.(12) shall deactivate all pumps serving the public spa and public pool.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.