3.10.4.3.Spatial Separations
(1) Except as provided in Sentences (2) to (4), the requirements in Subsection 3.2.3. shall apply.
(2) Where the building area conforms to Clause 3.10.4.2.(1)(b), the limiting distance requirements shall not apply
between individual buildings.
(3) Where the building area conforms to Clause 3.10.4.2.(1)(c),
(a) the limiting distance requirements shall apply between each group of buildings, but not between individual buildings
within a group, and
(b) the distance between each group of buildings shall be not less than 9 m.
(4) The distance between individual buildings within a group shall be not less than 6 m.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.