PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code

3.1.8.4.Determination of Ratings and Classifications

(1) Except as permitted by Sentences (2) and 3.1.8.16.(1), the fire-protection rating of a closure shall be determined in accordance with (a) CAN/ULC-S104, “Standard Method for Fire Tests of Door Assemblies,” (b) CAN/ULC-S106, “Standard Method for Fire Tests of Window and Glass Block Assemblies,” or (c) CAN/ULC-S112, “Standard Method for Fire Test of Fire Damper Assemblies.” (See Articles 3.1.8.17. to 3.1.8.19. for additional requirements for closures.) (2) Except as permitted by Sentence 3.1.8.12.(1), the fire-protection rating of a closure shall conform to Table 3.1.8.4. for the required fire-resistance rating of the fire separation. (3) The leakage rate of smoke dampers and combination smoke/fire dampers shall (a) be determined in accordance with the applicable provisions in CAN/ULC-S112.1, “Standard for Leakage Rated Dampers for Use in Smoke Control Systems,” and (b) conform to Class I, II or III of that standard. (4) The leakage rate of a door assembly shall be determined in accordance with ANSI/UL-1784, “Standard for Air Leakage Tests of Door Assemblies and Other Opening Protectives.” Table 3.1.8.4. Fire-Protection Rating of Closures Forming Part of Sentence 3.1.8.4.(2) Fire-Resistance Rating of Fire Separation Minimum Fire-Protection Rating of Closure 30 min 20 min 45 min 45 min 1h 45 min 1.5 h 1h 2h 1.5 h 3h 2h 4h 3h

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.