PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.8.16.Wired Glass and Glass Block
(1) Except as permitted by Articles 3.1.8.18. and 3.1.8.19. for the separation of exits, an opening in a fire separation
having a fire-resistance rating not more than 1 h is permitted to be protected with fixed wired glass assemblies or glass
blocks installed in conformance with NFPA 80, “Standard for Fire Doors and Other Opening Protectives.” (See also
Article 3.3.2.17.)
(2) Wired glass assemblies permitted by Sentence (1) and described in MMAH Supplementary Standard SB-2, “Fire
Performance Ratings,” are permitted to be used as closures in vertical fire separations without being tested in accordance
with Sentence 3.1.8.4.(1).
(3) Glass blocks permitted by Sentence (1) shall be installed in accordance with Subsection 4.3.2. and reinforced with
steel reinforcement in each horizontal joint.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.