PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.6.17.Penetration by Outlet Boxes
(1) The minimum dimensions stated in Table 3.1.6.3. need not apply at cutouts in vertical or horizontal structural mass
timber elements where outlet boxes are installed in accordance with Article 3.1.9.3. (See also Note A-3.1.9.2.(1))
(2) The exposed surfaces of the cutouts described in Sentence (1) need not be protected in accordance with Sentence
3.1.6.4.(1).
(3) Outlet boxes on opposite sides of a structural mass timber element having a fire-resistance rating shall be separated
by a distance of not less than 600 mm.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous3.1.6.16. Exposed Construction Materials and Components inNext →3.1.7.1. Determination of Ratings
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.