PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.6.10.Combustible Components in Exterior Walls
r1 (1) Except as provided in Sentence (2), combustible components, other than those permitted by Article 3.1.6.9., are
permitted to be used in an exterior wall assembly of a building or part thereof permitted to be of encapsulated mass
timber construction provided the wall assembly satisfies the criteria described in Clause 3.1.5.5.(1)(b).
(2) An exterior wall assembly constructed in conformance with Section 6 in MMAH Supplementary Standard SB-2,
“Fire Performance Ratings” is deemed to satisfy the criteria of Sentence (1).
(3) Non-loadbearing wood elements permitted in Article 3.1.5.6. need not conform to Article 3.1.6.3. in a building or
part of a building permitted to be of encapsulated mass timber construction.
Division B – Part 3 24a
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.