3.1.5.4.Combustible Windows, Glazing and Skylights
(1) Combustible skylight assemblies are permitted in a building required to be of noncombustible construction if the
assemblies have a flame-spread rating not more than
(a) 150 provided the assemblies
(i) have an individual area not more than 9 m2,
(ii) have an aggregate horizontal projected area of the openings through the ceiling not more than 25% of the area
of the ceiling of the room or space in which they are located, and
(iii) are spaced not less than 2.5 m from adjacent assemblies and 1 200 mm from required fire separations, or
(b) 75 provided the assemblies
(i) have an individual area not more than 27 m2,
(ii) have an aggregate horizontal projected area of the openings through the ceiling not more than 33% of the area
of the ceiling of the room or space in which they are located, and
(iii) are spaced not less than 1.2 m from adjacent assemblies and from required fire separations.
(See Note A-3.1.5.4.(1))
(2) Combustible vertical glazing installed no higher than the second storey is permitted in a building required to be of
noncombustible construction.
(3) Except as permitted by Sentence (4), the combustible vertical glazing permitted by Sentence (2) shall have a flame-
spread rating not more than 75.
(4) The flame-spread rating of combustible glazing is permitted to be not more than 150 if the aggregate area of glazing
is not more than 25% of the wall area of the storey in which it is located, and
(a) the glazing is installed in a building not more than 1 storey in building height,
(b) the glazing in the first storey is separated from the glazing in the second storey in accordance with the requirements
of Article 3.2.3.17. for opening protection, or
(c) the building is sprinklered throughout.
(5) Combustible window sashes and frames are permitted in a building required to be of noncombustible construction,
provided they are vertically non-contiguous between storeys.
← Previous3.1.5.3. Combustible Roofing MaterialsNext →3.1.5.5. Combustible Cladding on Exterior Walls
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.