3.1.5.21.Wires and Cables
(1) Except as permitted by Sentence (2) and Articles 3.1.5.22. and 3.1.5.25., optical fibre cables and electrical wires and
cables with combustible insulation, jackets or sheathes are permitted in a building required to be of noncombustible
construction, provided
(a) the wires and cables exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical
Flame Test – Cables in Cable Trays (FT4 rating) in CSA C22.2 No. 0.3, “Test methods for electrical wires and
cables,”
(b) the wires and cables are located in
(i) totally enclosed noncombustible raceways, (See Note A-3.1.4.3.(1)(b)(i))
(ii) masonry walls,
(iii) concrete slabs,
(iv) a service room separated from the remainder of the building by a fire separation having a fire-resistance
rating not less than 1 h, or
(v) totally enclosed non-metallic raceways conforming to Clause 3.1.5.23.(1)(b), or
(c) the wires and cables are communication cables used at the service entry to a building and are not more than 3 m
long.
(See Note A-3.1.5.21.(1))
(2) Except as permitted in Sentences (3) and (4), optical fibre cables and electrical wires and cables with combustible
insulation, jackets or sheathes that are used for the transmission of voice, sound or data and are not located in totally
enclosed noncombustible raceways are permitted to be installed in a plenum in a building required to be of
noncombustible construction, provided the wires and cables exhibit a horizontal flame distance of not more than 1.5 m, an
average optical smoke density of not more than 0.15, and a peak optical smoke density of not more than 0.5 when tested
in conformance with CAN/ULC-S102.4, “Standard Method of Test for Fire and Smoke Characteristics of Electrical
Wiring, Cables and Non-Metallic Raceways,” (FT6 rating).
(3) Except as permitted in Sentence (4), where totally enclosed noncombustible raceways are used in a plenum, exposed
components of wiring systems with combustible insulation, jackets or sheathes, including optical fibre cables and
electrical wires and cables that are used for the transmission of voice, sound or data, that are installed in the plenum or
that extend not more than 9 m from the plenum including drop down to the floor level, are permitted provided they exhibit
a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test – Cables in Cable Trays
(FT4 rating) in CSA C22.2 No. 0.3, “Test methods for electrical wires and cables.”
(4) Cables or wires within plenums that are used for the transmission of signals in fire alarm systems need not comply
with the requirements of Sentences (2) and (3).
← Previous3.1.5.20. Combustible Plumbing FixturesNext →3.1.5.22. Combustible Travelling Cables for Elevators
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.