PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.5.18.Combustible Ducts
(1) Except as required by Sentence 3.6.4.3.(1), combustible ducts, including plenums and duct connectors, are permitted
to be used in a building required to be of noncombustible construction provided these ducts and duct connectors are used
only in horizontal runs.
(2) Combustible duct linings, duct coverings, duct insulation, vibration isolation connectors, duct tape, pipe insulation
and pipe coverings are permitted to be used in a building required to be of noncombustible construction provided they
conform to the appropriate requirements of Subsection 3.6.5.
(3) In a building required to be of noncombustible construction, combustible ducts need not comply with the
requirements of Sentences 3.6.5.1.(1) and (2) provided the ducts are
(a) part of a duct system conveying only ventilation air, and
(b) contained entirely within a dwelling unit.
← Previous3.1.5.17. Storage Lockers in Residential BuildingsNext →3.1.5.19. Combustible Piping Materials
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.