3.1.5.10.Combustible Flooring Elements
(1) Combustible stage flooring supported on noncombustible structural members is permitted in a building required to
be of noncombustible construction.
(2) Wood members more than 50 mm but not more than 300 mm high applied directly to or set into a noncombustible
floor slab are permitted for the construction of a raised platform in a building required to be of noncombustible
construction provided the concealed spaces created are divided into compartments by fire blocks in conformance with
Sentence 3.1.11.3.(2).
(3) The floor system for the raised platform referred to in Sentence (2) is permitted to include combustible subfloor and
combustible finished flooring.
(4) Combustible finished flooring is permitted in a building required to be of noncombustible construction.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.