3.1.4.3.Wires and Cables
(1) Except as required by Sentence (2), optical fibre cables and electrical wires and cables with combustible insulation,
jackets or sheathes installed in a building permitted to be of combustible construction shall
(a) not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical Flame Test
(FT1 rating) in CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables,” or
(b) be located in
(i) totally enclosed noncombustible raceways, (See Note A-3.1.4.3.(1)(b)(i))
(ii) masonry walls,
(iii) concrete slabs, or
(iv) totally enclosed non-metallic raceways conforming to Clause 3.1.5.23.(1)(b).
(See Note A-3.1.4.3.(1)) (See also Sentence 3.6.4.3.(1))
(2) Except as permitted in Sentences (3) and (4), optical fibre cables and electrical wires and cables with combustible
insulation, jackets or sheathes that are used for the transmission of voice, sound or data and are installed in a plenum in a
building permitted to be of combustible construction shall exhibit the following characteristics when tested in
conformance with CAN/ULC-S102.4, “Standard Method of Test for Fire and Smoke Characteristics of Electrical Wiring,
Cables and Non-Metallic Raceways,” (FT6 rating):
(a) a horizontal flame distance of not more than 1.5 m,
(b) an average optical smoke density of not more than 0.15, and
(c) a peak optical smoke density of not more than 0.5.
(3) Except as permitted in Sentence (4), where totally enclosed noncombustible raceways are used in a plenum, exposed
components of wiring systems with combustible insulation, jackets or sheathes, including optical fibre cables and
electrical wires and cables that are used for the transmission of voice, sound or data, that are installed in the plenum or
that extend not more than 9 m from the plenum, including drop down to the floor level, are permitted, provided they
exhibit a vertical char of not more than 1.5 m when tested in conformance with the Vertical Flame Test – Cables in Cable
Trays (FT4 rating) in CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables.”
(4) Cables or wires within plenums that are used for the transmission of signals in fire alarm systems need not comply
with the requirements of Sentence (2).
← Previous3.1.4.2. Protection of Foamed Plastics (See Note A-3.1.4.Next →3.1.4.4. Non-metallic Raceways
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.