3.1.13.4.Light Diffusers and Lenses
(1) The flame-spread rating of combustible light diffusers and lenses in all occupancies other than Group A, Division 1
is permitted to be more than the flame-spread rating limits required elsewhere in this Subsection, provided the light
diffusers and lenses
(a) have a flame-spread rating not more than 250 and a smoke developed classification not more than 600 when tested
in conformance with CAN/ULC-S102.2, “Standard Method of Test for Surface Burning Characteristics of Flooring,
Floor Coverings, and Miscellaneous Materials and Assemblies,”
(b) fall to the bottom of the test apparatus before igniting when tested in conformance with CAN/ULC-S102.3,
“Standard Method of Fire Test of Light Diffusers and Lenses,”
(c) are not prevented from falling from the ceiling by construction located beneath the elements, and
(d) are not used in a corridor that is required to be separated from the remainder of the building by a fire separation or
in an exit shaft unless individual diffusers or lenses are not more than 1 m 2 in area and are not less than 1.2 m apart.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.