(1) The wall and ceiling finishes of an exterior exit passageway that provides the only means of egress from the rooms
or suites it serves, including the soffit beneath and the guard on the passageway, shall have a flame-spread rating not
more than 25, except that a flame-spread rating not more than 150 is permitted for up to 10% of the total wall area and for
up to 10% of the total ceiling area.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.