PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.12.1.Determination of Ratings
(1) Except as required by Sentence (2) and as permitted by Sentence (3), the flame-spread rating and smoke developed
classification of a material, assembly, or structural member shall be determined on the basis of not less than three tests
conducted in conformance with CAN/ULC-S102, “Standard Method of Test for Surface Burning Characteristics of
Building Materials and Assemblies.”
(2) The flame-spread rating and smoke developed classification of a material or assembly shall be determined on the
basis of not less than three tests conducted in conformance with CAN/ULC-S102.2, “Standard Method of Test for Surface
Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies,” if the material or
assembly
(a) is designed for use in a relatively horizontal position with only its top surface exposed to air,
(b) cannot be tested in conformance with Sentence (1) without the use of supporting material that is not representative
of the intended installation, or
(c) is thermoplastic.
(3) A material, assembly, or structural member is permitted to be assigned a flame-spread rating and smoke developed
classification on the basis of MMAH Supplementary Standard SB-2, “Fire Performance Ratings.”
← Previous3.1.11.7. Fire Block MaterialsNext →3.1.13.1. Interior Finishes, Furnishings and Decorative Ma
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.