3.1.11.2.Fire Blocks in Wall Assemblies
(1) Except as permitted by Sentence (2), fire blocks conforming to Article 3.1.11.7. shall be provided to block off
concealed spaces within a wall assembly
(a) at every floor level,
(b) at every ceiling level where the ceiling forms part of an assembly required to have a fire-resistance rating, and
(c) so that the maximum horizontal dimension is not more than 20 m and the maximum vertical dimension is not more
than 3 m.
(2) Fire blocks conforming to Sentence (1) are not required provided
(a) the wall space is filled with insulation,
(b) the exposed construction materials and any insulation within the wall space are noncombustible,
(c) the exposed materials within the wall space, including insulation but not including wiring, piping or similar services,
have a flame-spread rating not more than 25 on any exposed surface, or on any surface that would be exposed by
cutting through the material in any direction, and fire blocks are installed so that the vertical distance between them
is not more than 10 m, or
(d) the insulated wall assembly contains not more than one concealed air space, and the horizontal thickness of that air
space is not more than 25 mm.
← Previous3.1.11.1. Separation of Concealed SpacesNext →3.1.11.3. Fire Blocks Between Nailing and Supporting Eleme
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.