PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.10.7.Combustible Projections
(1) Combustible material shall not extend across the end of a firewall but is permitted to extend across a roof above a
firewall that is terminated in conformance with Sentence 3.1.10.3.(2).
(2) If buildings are separated by a firewall, combustible projections on the exterior of one building, including balconies,
platforms, canopies, eave projections and stairs, that extend outward beyond the end of the firewall, shall not be permitted
within 2.4 m of combustible projections and window or door openings of the adjacent building. (See also Article 3.2.3.6.)
← Previous3.1.10.6. Exposure Protection for Adjacent WallsNext →3.1.11.1. Separation of Concealed Spaces
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.