PART 2 — RESERVEDUpdated for the 2024 Ontario Building Code

2.3.4.1.Application Limitation

(1) Farm buildings need not be designed for loads due to earthquakes in accordance with Subsection 4.1.8. where (a) the Seismic Category is SC1, or (b) the Seismic Category is SC2, and the RdRo value of the seismic force resisting system (SFRS) is equal to or greater than 3.0. (See Note A-2.3.4.1.(1)(b)) (2) For the purpose of Sentence (1), the Seismic Category is permitted to be determined on the basis of I ES(0.2) alone. (3) For the purpose of Sentences (1) and (2), the Seismic Category is permitted to be determined by assigning Site Class D without carrying out a subsurface investigation.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.