12.3.1.3.Temperature Control in Houses and Dwelling Units
(1) Except as provided in Sentence (3) and except where space heating energy is provided by a solid fuel-burning
appliance or a ground source heat pump,
(a) heating system in an individual dwelling unit shall be controlled by at least one programmable thermostatic control
device located in the dwelling unit, and
(b) where a house contains a secondary suite, each dwelling unit shall be controlled by at least one programmable
thermostatic control device located in the dwelling unit.
(2) The programmable thermostatic control device required in Sentence (1) shall
(a) allow the setting of different air temperatures for at least
(i) four time periods per day, and
(ii) two different day-types per week,
(b) include a manual override, and
(c) allow the setting of the air temperature to
(i) 13°C or lower in heating mode, and
(ii) 29°C or higher in cooling mode, where air-conditioning is provided.
(3) A manual thermostatic control device is permitted if it
(a) controls a heating or cooling system where the heating or cooling capacity is not more than 2 kW, or
(b) serves an individual room or space.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.