PART 11 — RENOVATIONUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
11.4.2.2.Increase in Occupant Load
(1) Except as provided in Sentences 11.4.2.5.(2) and (3), the performance level of an existing building is reduced where
proposed construction will increase the occupant load of an existing building by more than 15%.
(2) The performance level of an existing building is reduced where proposed construction will increase the occupant
load by 15% or less and the new occupant load will be more than 15% above the occupant load for which a fire alarm
system is required under Sentence 3.2.4.1.(2).
(3) The performance level of an existing building is reduced where proposed construction will increase the occupant
load by 15% or less and the new occupant load will be more than 15% above the existing exit capacity as required under
Article 3.4.3.2.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.